Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
Tel: 01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
www.powersolve.co.uk
Uninterruptible Power Supplies
Models and Ratings
MODEL OUTPUT POWER OUTPUT CURRENT AUTONOMY
VA Watts (at 230VAC) (full load)
Xi1000 1000VA 700W 4.3A 12 Minutes
Xi1500 1500VA 1050W 6.5A 9 Minutes
Xi2500 2500VA 1750W 10.8A 9 Minutes
Xi3000 3000VA 2100W 13.0A 7 Minutes
Xi4000 4000VA 2800W 17.3A 12 Minutes
Xi5000 5000VA 3500W 21.7A 9 Minutes
Xi6000 6000VA 4200W 26.0A 7 Minutes
MODEL OUTPUT POWER OUTPUT CURRENT AUTONOMY
VA Watts (at 115VAC) (full load)
Xi1500L CE 1500VA 1050W 13.0A 5 Minutes
Xi3000L 120 3000VA 2100W 26.0A 5 Minutes
Accessory Products
Xi 232 RS232 Option Card giving second RS232 function
Xi BM 110C Battery modules for Xi series UPS - fitted with 2 x Xi BP with additional 110V input charger for extended run times
Xi BP Battery pack - contains 4 x 7Ahr VRLA 5 year design life batteries
Xi BMC Battery module for Xi series UPS - populated with 2 x Xi BP, with additional charger for extended run times
Xi BB1K5
(1)
Make before break dual input multi format bypass module for Xi1000 & Xi1500.
Provides safety interlock when used with Xi V.
Xi BB3K
(1)
Make before break dual input multi format bypass module for Xi2500 & Xi3000.
Provides safety interlock when used with Xi V.
Xi BB6K
(1)
Make before break dual input multi format bypass module for Xi4000 & Xi6000.
Provides safety interlock when used with Xi V.
Xi R Telescopic rack guides for UPS and battery modules
Xi S SNMP Network Adaptor Option Card replaces USB port, allowing the UPS to be addressed directly on the LAN
Xi V
AS400 Volt Free Contact Option Card replaces USB comms port with a 15 way D-type connector
Providing Utility Fail, Battery Low, Bypass & UPS Alarm Contacts
(1). Unit can be used without Xi V. However, there is no automatic protection against bypass operation while the unit is on inverter. Units must operate
with common neutral. Contact sales office for details.
Option Order Codes
Power (VA) Options
(1)
E.G. Xi1000RX
Xi Series, 1000VA
With telescopic rail guides and 10 year design life batteries fitted
Options (Examples)
Add suffix ‘R’ to Model Number - Adds rack guides to unit for 19” rack mounting
Add suffix ‘S’ to Model Number - Adds internal SNMP to UPS (in place of USB port)
Add suffix ‘V’ to Model Number - Adds AS400 VFC to UPS for Utility Fail, Bypass, Battery Low and UPS Fault (in place of USB port)
Add suffix ‘X’ to Model Number - Replaces 5 year design life batteries with 10 year